DJYVP Overall Screened Instrumentation Cable
DJYVP-300/500V
PE-insulated pairs under one copper braid screen, for analogue and digital runs of a single signal class.
Instrumentation cable carries the signal that the control system acts on, and its construction is defined by capacitance, crosstalk and shielding geometry rather than by current ra
Instrumentation cable carries the signal that the control system acts on, and its construction is defined by capacitance, crosstalk and shielding geometry rather than by current rating. Polyethylene insulation keeps mutual capacitance near 50–60 pF/m against 90–130 pF/m for a PVC pair, conductors are twisted into pairs with a short, controlled lay length so that an external field induces equal and opposite voltages in the two legs, and the screen is placed where the interference study says it belongs.
The DJ family used in China encodes that decision in the type designation: the position of the P tells you whether the braid sits over each pair, over the whole bundle, or over both. Voltcore builds the DJ range to GB/T with 1 to 24 pairs in 0.5–2.5 mm², and supplies the DIN VDE equivalents — RE-2Y(St)Y PiMF with DIN 47100 colour coding and blue sheath for intrinsically safe circuits — on the same production lines for European projects.
DJYVP-300/500V
PE-insulated pairs under one copper braid screen, for analogue and digital runs of a single signal class.
DJYPV-300/500V
A braid over every pair, so crosstalk between channels stops at the pair boundary.
DJYPVP-300/500V
The default specification when analogue, digital and switching channels share one cable.
RE-2Y(St)Y-300/500V
The European equivalent of the DJ range: PE pairs, static screen, DIN 47100 identification.
BUS-485-120R
Impedance-controlled twisted pair for RS-485, Profibus DP and Modbus RTU segments.
An overall screen stops interference entering the cable. It does nothing about interference generated inside it: a 24 V DC solenoid circuit switched in the same bundle will induce a spike into an adjacent 4–20 mA pair, and no overall braid prevents that. Individual pair screens put a grounded barrier between the pairs, which is what PiMF — pairs in metal foil — exists to do.
The practical test is whether one cable carries mixed signal classes. A bundle that is entirely 4–20 mA loops, or entirely digital, is adequately served by an overall screen. The moment a switching circuit, a pulse train or a 100 mV thermocouple shares the sheath, specify individual screens and accept the larger diameter.
A two-wire transmitter needs the loop supply to exceed the sum of the transmitter minimum operating voltage, the receiver burden and the voltage lost in the cable. A typical transmitter needs 12 V, a 250 Ω receiver drops 5 V at 20 mA, and the cable drops 2 × loop length × resistance per kilometre. Work the arithmetic on the return pair, not on one core.
At 1.5 mm² (12.1 Ω/km) a 1 000 m loop returns 24.2 Ω of cable, dropping 0.48 V at 20 mA — comfortable. At 0.5 mm² the same loop returns 72 Ω and drops 1.45 V, which still works but leaves little margin for a long run in a hot tray where resistance rises with temperature.
In an Ex i installation the cable is part of the safety calculation, not just a conductor. The total capacitance and inductance of the loop — cable plus field device — must stay within the limits certified for the associated apparatus, so the cable datasheet has to state mutual capacitance and L/R ratio, not merely construction.
Identification and segregation matter as much as the numbers. Intrinsically safe circuits are identified by a light blue sheath and must be separated from non-IS circuits by at least 50 mm, by a grounded metal screen, or by an insulating divider, to prevent a fault transferring energy across.
Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.
RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.