KVV PVC Control Cable
KVV-450/750V
The standard unscreened PVC control cable for switchgear, MCC cubicles and plant interlocks.
The K family of PVC control cable is the default wiring material inside Chinese-built switchgear, MCC line-ups and plant control panels. Rated 450/750 V and built to GB/T 9330, it
The K family of PVC control cable is the default wiring material inside Chinese-built switchgear, MCC line-ups and plant control panels. Rated 450/750 V and built to GB/T 9330, it covers 2 to 61 cores in 0.75–10 mm², with the type suffix telling you exactly what sits between the copper and the sheath: nothing for KVV, a copper wire braid for KVVP, a copper tape for KVVP2, Class 5 flexible stranding for KVVR, or XLPE insulation for KYJV.
Choosing between those five is mostly a question of EMC and temperature. A braid screen suits a run alongside a motor feeder or a VFD; a tape screen suits a fixed RF-sensitive run where budget matters; flexible stranding suits machine-tool carriers and door harnesses. Voltcore produces all five on dedicated lines at its Yixing plant, with ZR flame-retardant and WDZ low-smoke halogen-free sheath compounds available on every one.
KVV-450/750V
The standard unscreened PVC control cable for switchgear, MCC cubicles and plant interlocks.
KVVP-450/750V
Braid-screened control cable with a low-resistance shield path for VFD leads and long analogue runs.
KVVP2-450/750V
Copper tape screen at 100 % coverage for fixed runs that must reject high-frequency interference.
KVVR-450/750V
Class 5 fine-wire conductors for control circuits that move, bend or vibrate.
KYJV-450/750V
XLPE insulation for control circuits in hot plant, high fault levels and long de-rated runs.
KVVP carries a braid of 0.12–0.20 mm copper wires at 80–90 % coverage; KVVP2 wraps a 0.05 mm copper tape at effectively 100 % coverage. The difference that matters on site is not the coverage figure but the resistance of the shield path: a braid offers a low-resistance drain route, which is what suppresses the 2–20 kHz common-mode current a VFD pushes into the motor cable.
Tape wins on high-frequency performance and on price, because a continuous foil has no apertures and uses less copper. It is the right screen for fixed installation inside a panel or a rack where the cable is never flexed after termination. Where the cable must move, or where the circuit is an analogue loop within a few metres of a drive, specify the braid.
PVC/A insulation is rated 70 °C continuous with a 160 °C short-circuit limit for 5 s, which covers most cubicle and plant wiring. KYJV replaces it with cross-linked polyethylene rated 90 °C continuous and 250 °C short-circuit, so the same cross-section carries more current or survives a fault with more margin.
The second reason is ambient heat. A cable tray on a Middle East roof or inside a steel mill can sit above 60 °C ambient, and de-rating a PVC cable into that environment often forces a size increase that costs more than the XLPE upgrade. Where the circuit is long and the load is inductive, check voltage drop before deciding.
Control cables are usually installed once and modified many times, so core count deserves more thought than cross-section. A common rule on plant projects is 20 % spare cores, with a minimum of two spares on any cable above 7 cores; panel builders often standardise on 12-core and 19-core constructions so that one drum covers several drawings.
Cross-section is governed by voltage drop and by terminal capacity rather than by current alone. A 1.5 mm² core at 20 °C has a maximum resistance of 12.1 Ω/km, so a 200 m run of a 24 V DC solenoid drawing 2 A drops roughly 9.7 V across the pair unless you go up to 2.5 mm².
Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.