KVVP-450/750V
KVVP Copper Wire Braid Screened PVC Control Cable — 450/750 V
Braid-screened control cable with a low-resistance shield path for VFD leads and long analogue runs.
KVVP takes the KVV construction and inserts a braid of 0.12–0.20 mm annealed copper wires over the laid-up bundle, typically at 80–90 % optical coverage, with a tinned drain wire laid against the braid for termination. That braid is what makes KVVP the correct answer for VFD output leads and analogue runs near power conductors: at the 2–20 kHz carrier frequencies a drive generates, shield performance is governed by the resistance of the shield path, and a braid of copper wires carries that current far better than a thin foil.
The braid is also the reason KVVP survives installation abuse. It flexes with the cable, keeps coverage when the cable is bent around a motor terminal box, and gives the gland something substantial to clamp onto. Voltcore builds KVVP to GB/T 9330 with the braid angle held at 30–45° so that coverage does not open up when the cable is pulled through a tray; higher coverage classes and a composite foil plus braid screen are available where the EMC study calls for them.
Specification
| Item | Value |
|---|---|
| Rated voltage U0/U | 450/750 V |
| Conductor | Class 2 stranded plain annealed copper, IEC 60228 |
| Number of cores | 2 – 61 |
| Cross-section range | 0.75 – 10 mm² |
| Insulation | PVC/A, 70 °C rated |
| Screen | Copper wire braid, 0.12–0.20 mm wire, 80–90 % coverage, with tinned copper drain wire |
| Sheath | PVC ST1 black, flame-retardant grades available |
| Max. continuous conductor temperature | 70 °C |
| Test voltage | 2.5 kV rms for 5 min (core to core and core to screen) |
| Minimum bending radius | 15 × cable overall diameter |
| Screen termination | 360° clamp or EMC cable gland recommended |
| Installation temperature | Not below 0 °C |
Layer-by-layer construction
Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.
- 1. ConductorStranded plain annealed copper, Class 2 to IEC 60228
- 2. InsulationPVC/A extruded per core, 0.6–1.0 mm wall, colour or number identified
- 3. Lay-up and fillerCores laid up in concentric layers with non-hygroscopic PP fillers for circularity
- 4. Binder tapePolyester tape over the bundle to hold the lay before screening
- 5. ScreenCopper wire braid at 80–90 % coverage with a tinned copper drain wire in continuous contact
- 6. SheathBlack PVC ST1, 1.2–1.6 mm nominal, extruded over the braid
Reference dimensions and weights
| Cores × cross-section (mm²) | Conductor structure (No./mm) | Insulation thickness (mm) | Braid wire diameter (mm) | Sheath thickness (mm) | Approx. overall diameter (mm) | Approx. weight (kg/km) | Max. DC resistance at 20 °C (Ω/km) |
|---|---|---|---|---|---|---|---|
| 4×0.75 | 7/0.37 | 0.6 | 0.12 | 1.2 | 8.7 | 155 | 24.5 |
| 4×1.0 | 7/0.43 | 0.6 | 0.12 | 1.2 | 9.1 | 175 | 18.1 |
| 4×1.5 | 7/0.52 | 0.7 | 0.15 | 1.2 | 10.2 | 225 | 12.1 |
| 4×2.5 | 7/0.68 | 0.7 | 0.15 | 1.4 | 11.3 | 300 | 7.41 |
| 4×4 | 7/0.85 | 0.8 | 0.15 | 1.4 | 13.2 | 400 | 4.61 |
| 4×6 | 7/1.04 | 0.8 | 0.20 | 1.4 | 14.6 | 520 | 3.08 |
| 4×10 | 7/1.35 | 1.0 | 0.20 | 1.6 | 18.0 | 760 | 1.83 |
Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.
Engineering characteristics
- Copper wire braid at 80–90 % coverage with a drain wire, giving a low-resistance shield path at power frequency and up to VFD carrier frequencies
- Braid stays effective after bending, so the cable suits motor terminal boxes and machine-mounted runs
- 450/750 V rating, 2.5 kV rms for 5 min test voltage including core to screen
- PVC/A insulation rated 70 °C continuous, 160 °C for 5 s short circuit
- Screen resistance measured per drum; typical loop resistance of the braid plus drain wire is under 15 Ω/km
- Minimum bending radius 15 × cable overall diameter during installation
- Available with ZR-KVVP and WDZ-KVVP sheath compounds, and as KVVP22 with steel tape armour
Typical applications
- Variable frequency drive output and motor leads where common-mode current must return to the drive
- Analogue 4–20 mA and 0–10 V loops running in a tray shared with power conductors
- PLC and DCS marshalling cubicles with long field cable runs
- Encoder, resolver and pulse feedback wiring on machine tools
- Substation control and protection wiring adjacent to switchyard cabling
Ordering options
- Higher braid coverage (up to 95 %) or a foil plus braid composite screen
- ZR-KVVP and WDZ-KVVP halogen-free sheath compounds
- KVVP22: steel tape armoured, 12 × overall diameter minimum bending radius
- Individually screened cores or pairs in place of the overall braid
- Tinned copper braid for marine and coastal installations
Standards manufactured to
- GB/T 9330
- IEC 60228 (conductor)
- GB/T 19666 (flame-retardant grades)
- IEC 60332-1-2 (flame propagation)
- GB/T 3048 (electrical test methods)
- RoHS and REACH compliant compounds
Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.
Price and availability for KVVP Copper Braid Screened Control Cable
Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.
- Engineer-reviewed before pricing
- Reference drawings issued with the quotation
- Free sample up to free sample up to 5 m
KVVP Copper Braid Screened Control Cable — frequently asked questions
Should I choose a braid screen or a tape screen for a VFD motor lead?
Choose the braid. A VFD carrier sits between roughly 2 kHz and 20 kHz, where shield performance follows the resistance of the shield path; a braid of copper wires offers far lower resistance than a 0.05 mm tape. The braid also survives the bend at the motor terminal box, where foil tears.
What braid coverage does KVVP give, and can I get more?
Standard production is 80–90 % optical coverage, verified by weighing the braid against the theoretical mass. Where 95 % or a foil plus braid composite is needed, Voltcore quotes it as a modified construction; expect a larger overall diameter and a higher kg/km figure than the reference table.
Do I need to earth the screen at both ends?
For VFD and mixed-frequency installations, yes — terminate 360° at both ends using an EMC gland or a metal clamp so that the shield carries the common-mode current. For a pure 50/60 Hz analogue loop, earthing at one end only avoids a ground-loop current in the screen.
Is KVVP the same as KVVRP?
No. KVVP uses Class 2 stranded conductors for fixed installation; KVVRP uses Class 5 fine-wire conductors and is intended for flexible connections. If the cable moves after installation — a machine carriage, a door harness, a drag chain — specify KVVRP.
Related technical resources
Chinese Cable Type Codes Explained: YJV, VV, KVV, DJYPVP...
A Chinese cable type code looks like alphabet soup until you know that it is built in blocks: what the insulation is, what the con…
Read → Selection Guide · 10 minVFD and Servo Cable Selection: Why Screened Cable Matters More Than You Think
The cable between a drive and a motor is not carrying a sine wave. It is carrying a train of fast-edged pulses, and that changes w…
Read →