KVVP2-450/750V

KVVP2 Copper Tape Screened PVC Control Cable — 450/750 V

Copper tape screen at 100 % coverage for fixed runs that must reject high-frequency interference.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

KVVP2 replaces the braid of KVVP with a helically applied copper tape, normally 0.05 mm, laid with an overlap so the shield is continuous along the whole length. Coverage is effectively 100 %, which removes the apertures a woven braid always leaves and makes the screen markedly better against interference above about 1 MHz — fast switching transients, radio transmitters, and the harmonics that a poorly filtered drive throws back into the supply.

The trade-off is mechanical and electrical at low frequency. A 0.05 mm tape carries higher DC resistance than a braid, so its transfer impedance at power frequency is worse, and repeated bending work-hardens and tears it. KVVP2 is therefore a fixed-installation cable: racked, cleated or trunked, installed once and left alone. It also uses less copper, so it costs less than a comparable KVVP, which is why it is common on panel-internal wiring and on long runs where budgets are tight.

Specification

KVVP2 450/750 V — Technical Specification
ItemValue
Rated voltage U0/U450/750 V
ConductorClass 2 stranded plain annealed copper, IEC 60228
Number of cores2 – 61
Cross-section range0.75 – 10 mm²
InsulationPVC/A, 70 °C rated
ScreenCopper tape, 0.05 mm nominal, helically applied with overlap, 100 % coverage
Drain wireTinned copper, laid in continuous contact with the tape
SheathPVC ST1 black, flame-retardant grades available
Max. continuous conductor temperature70 °C
Test voltage2.5 kV rms for 5 min (core to core and core to screen)
Minimum bending radius15 × cable overall diameter
Installation temperatureNot below 0 °C

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorStranded plain annealed copper, Class 2 to IEC 60228
  2. 2. InsulationPVC/A per core, 0.6–1.0 mm wall, colour or number identified
  3. 3. Lay-up and fillerConcentric lay-up with non-hygroscopic PP fillers for a circular section
  4. 4. Binder tapePolyester tape applied over the bundle before screening
  5. 5. ScreenCopper tape 0.05 mm applied helically with overlap for continuous 100 % coverage, with tinned drain wire
  6. 6. SheathBlack PVC ST1, 1.2–1.6 mm nominal

Reference dimensions and weights

KVVP2 450/750 V — 4-core dimensions and weight (reference figures)
Cores × cross-section (mm²)Conductor structure (No./mm)Insulation thickness (mm)Copper tape thickness (mm)Sheath thickness (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)
4×0.757/0.370.60.051.28.314024.5
4×1.07/0.430.60.051.28.715818.1
4×1.57/0.520.70.051.29.720012.1
4×2.57/0.680.70.051.410.82687.41
4×47/0.850.80.051.412.63554.61
4×67/1.040.80.051.414.04553.08
4×107/1.351.00.051.617.46651.83

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Continuous copper tape screen with no braid apertures, effective against interference above roughly 1 MHz
  • Lower shield DC resistance path than foil-only constructions because the drain wire is bonded along the tape
  • Lower copper content than an equivalent braid screen, which reduces both price and kg/km
  • 450/750 V rating, 2.5 kV rms for 5 min including core to screen
  • PVC/A insulation rated 70 °C continuous, 160 °C for 5 s short circuit
  • Smaller overall diameter than KVVP at the same core count, so more cores fit one gland
  • Supplied with ZR-KVVP2 and WDZ-KVVP2 sheath compounds on request

Typical applications

  • Panel-internal wiring where RF fields or fast transients corrupt unshielded circuits
  • Telemetry and SCADA cable runs inside control buildings and rack rooms
  • Long fixed cable racks on water, wastewater and district heating schemes
  • Signal wiring near radio transmitters, radar and induction heating equipment
  • Replacement runs on existing installations where gland size is already fixed

Ordering options

  • Composite foil plus braid screen where both low-frequency and RF performance are required
  • ZR-KVVP2 flame-retardant and WDZ-KVVP2 low-smoke halogen-free sheath compounds
  • KVVP2-22: steel tape armour for burial and exposed mechanical duty
  • Aluminium foil plus tinned drain wire as a lower-cost screen alternative
  • Numbered, DIN 47100 or customer-specified core identification

Standards manufactured to

  • GB/T 9330
  • IEC 60228 (conductor)
  • GB/T 19666 (flame-retardant grades)
  • IEC 60332-1-2 (flame propagation)
  • GB/T 3048 (electrical test methods)

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for KVVP2 Copper Tape Screened Control Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

KVVP2 Copper Tape Screened Control Cable — frequently asked questions

Why is KVVP2 cheaper than KVVP at the same size?

A 0.05 mm tape uses far less copper than a woven braid of 0.12–0.20 mm wires, and it is applied in one pass rather than on a braiding machine. The saving is real but comes with less flexibility and a higher-resistance shield path at low frequency.

Can KVVP2 be used on a moving machine part?

No. Repeated bending work-hardens the tape and it cracks, opening the shield at the bend. For any moving application use a braid screen — KVVRP if the conductors also need to be Class 5 flexible, or a purpose-built drag chain cable.

Is 100 % coverage always better than 90 % braid coverage?

Not at every frequency. Coverage governs high-frequency leakage, so the tape wins there. At power frequency and at VFD carrier frequencies the deciding factor is the resistance of the shield path, and a braid wins that comparison. Match the screen to the interference spectrum.

How do I terminate the copper tape screen?

Fold the tape back over the sheath and clamp it with a metal screen clamp or an EMC gland so the contact is circumferential. Do not twist the drain wire into a pigtail — the added inductance defeats the screen above a few hundred kilohertz.