KVV-450/750V

KVV PVC Insulated and Sheathed Control Cable — 450/750 V

The standard unscreened PVC control cable for switchgear, MCC cubicles and plant interlocks.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

KVV is the benchmark control cable in Chinese-built switchgear and MCC line-ups: PVC/A insulation over Class 2 plain annealed copper, laid up with non-hygroscopic fillers, bound with polyester tape and finished in a black PVC ST1 sheath. It is specified for 450/750 V control circuits — contactor coils, interlock strings, solenoid valves, annunciator panels — where the signal is a switching state rather than an analogue value and no screen is required. Voltage drop, core count and termination density drive the selection, not capacitance.

Because KVV carries no screen, it belongs in panels and racks that are physically separated from power conductors; the usual rule is 300 mm clearance from cables above 1 kV, or a grounded steel divider in a shared tray. Voltcore supplies KVV from its Yixing plant with ZR and WDZ sheath compounds, tinned conductors for humid sites, and KVV22 steel-tape armour where the run leaves the tray. Core identification can be numbered, colour-coded to DIN 47100, or matched to a customer sequence.

Specification

KVV 450/750 V — Technical Specification
ItemValue
Rated voltage U0/U450/750 V
ConductorClass 2 stranded plain annealed copper, IEC 60228
Number of cores2, 3, 4, 5, 7, 8, 10, 12, 14, 16, 19, 24, 27, 30, 37, 44, 48, 52, 61
Cross-section range0.75 – 10 mm²
InsulationPVC/A, 70 °C rated
SheathPVC ST1 black; ST2 or flame-retardant grades on request
Max. continuous conductor temperature70 °C
Short-circuit conductor temperature160 °C for 5 s maximum
Test voltage2.5 kV rms for 5 min, no breakdown
Minimum bending radius15 × cable overall diameter (unarmoured)
Installation temperatureNot below 0 °C
Core identificationNumbered print, colour coded, or DIN 47100

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorStranded plain annealed copper, Class 2 to IEC 60228, 7-wire construction from 0.75 mm² to 10 mm²
  2. 2. InsulationPVC/A compound extruded over each conductor, 0.6–1.0 mm wall according to cross-section
  3. 3. Lay-upCores stranded in concentric layers with a lay length of 14–20 × core bundle diameter
  4. 4. FillerNon-hygroscopic polypropylene fillers in the interstices to hold a circular section
  5. 5. BinderPolyester tape applied longitudinally or helically over the laid-up bundle
  6. 6. SheathBlack PVC ST1, 1.2–1.6 mm nominal, extruded pressure-tight over the binder

Reference dimensions and weights

KVV 450/750 V — 4-core dimensions and weight (reference figures)
Cores × cross-section (mm²)Conductor structure (No./mm)Insulation thickness (mm)Sheath thickness (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)
4×0.757/0.370.61.27.69224.5
4×1.07/0.430.61.28.010818.1
4×1.57/0.520.71.29.114512.1
4×2.57/0.680.71.210.22057.41
4×47/0.850.81.412.12924.61
4×67/1.040.81.413.43953.08
4×107/1.351.01.616.86101.83

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • 450/750 V rating with 2.5 kV rms for 5 min test voltage per GB/T 3048
  • PVC/A insulation rated 70 °C continuous and 160 °C for 5 s short circuit
  • Class 2 copper to IEC 60228, with DC resistance verified on every production length
  • 2 to 61 cores in 0.75–10 mm², laid up in concentric layers for a circular section
  • PVC ST1 sheath; ZR-KVV to GB/T 19666 and WDZ-KVV low-smoke halogen-free on request
  • Minimum bending radius 15 × cable overall diameter, 12 × for the KVV22 armoured variant
  • Numbered, DIN 47100 or customer-specific core identification printed at 25–50 mm pitch

Typical applications

  • Contactor coil and interlock wiring inside MCC and switchgear cubicles
  • Solenoid valve and actuator control circuits in water treatment and HVAC plant
  • Annunciator, relay and protection panel wiring in substations up to 450/750 V
  • Machine control consoles and operator desks fed from 230/400 V control transformers
  • Building services: fire damper, pump and fan start-stop circuits

Ordering options

  • ZR-KVV: flame-retardant sheath to GB/T 19666 Class A, B or C
  • WDZ-KVV: low-smoke zero-halogen sheath to IEC 60754-1 and IEC 61034-2
  • KVV22: steel tape armoured for direct burial and trench runs
  • Tinned copper conductor for marine, coastal or high-humidity sites
  • Cut-to-length packing, OEM drum printing and private-label sheath marking

Standards manufactured to

  • GB/T 9330
  • IEC 60228 (conductor)
  • GB/T 3048 (electrical test methods)
  • GB/T 19666 (flame-retardant and fire-resistant grades)
  • IEC 60332-1-2 (single cable flame test)
  • RoHS and REACH compliant compounds

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for KVV PVC Control Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

KVV PVC Control Cable — frequently asked questions

What does the type designation KVV actually mean?

K marks it as a control cable to GB/T 9330, the first V denotes PVC insulation and the second V denotes a PVC sheath. No letter for screening appears, so the cable is unscreened by definition. Rated voltage is 450/750 V, meaning 450 V to earth and 750 V between conductors.

Can KVV be installed outdoors or buried directly?

The PVC ST1 sheath is UV-stabilised and moisture-resistant, but it is not rated for soil stress or mechanical damage. For direct burial use KVV22 with steel tape armour, or run KVV in conduit. In sunlight, expect a reduced service life unless a UV-resistant black sheath compound is specified.

How is KVV different from KVVP?

KVVP adds a copper wire braid screen, normally 80–90 % coverage with a tinned drain wire, beneath the sheath. That screen gives induced noise a low-resistance path to earth, which KVV cannot provide. KVVP costs more and has a larger overall diameter, so it is specified only where the EMC study requires it.

What is the minimum order quantity and can sizes be mixed?

Voltcore works to 500 m per size and cross-section. Different sizes can be combined in one 20 ft container from Shanghai or Ningbo, with delivery in 15–25 working days. Samples of up to 5 m are free, and payment is T/T 30 % deposit, L/C at sight, or Western Union for sample freight.

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.