Chinese Cable Type Codes Explained: YJV, VV, KVV, DJYPVP...

A Chinese cable type code looks like alphabet soup until you know that it is built in blocks: what the insulation is, what the conductor is, what the armour is, and what the outer sheath is. Once the blocks are separated, YJV and YJLV32 stop being strings of letters and start being a specification. This page decodes the system letter by letter, including the fire performance prefixes and the control and instrument cable families, and then reads a real sheath marking end to end.

By Voltcore Technical Team Published 2026-09-05

The code is built in blocks, not at random

Every type code in the GB/T 12706 and JB/T 8734 families follows the same logic. Reading from left to right, the first letters describe the insulation and, if it is not copper, the conductor. Any prefix before that describes the fire performance. The digits at the end describe the armour and then the outer sheath. Nothing else is hidden in the code: the voltage rating, the number of cores and the cross-section are always written separately, as 0.6/1 kV and 4 × 95, because they are not part of the type.

Take YJV22 as the worked example. YJ is XLPE insulation. The absence of a conductor letter means copper. The first 2 is double steel tape armour. The second 2 is a PVC outer sheath. So YJV22 is an XLPE insulated, copper, steel tape armoured, PVC sheathed cable, and it needs 0.6/1 kV and 4 × 95 written next to it to be complete. Change any block and you have a different cable: YJLV22 is the same thing with an aluminium conductor, YJV23 has a polyethylene outer sheath, YJV32 has steel wire armour.

Letter glossary for the GB/T 12706 and JB/T 8734 type codes
Letter or digitMeaningWhere it appears in the code
YJXLPE, cross-linked polyethylene insulationFirst block, insulation
YPolyethylene, PE insulationFirst block, insulation
VPVC, as insulation or as outer sheath depending on positionFirst block or final sheath position
LAluminium conductor; its absence means copperAfter the insulation letter
TCopper conductor, usually omitted because copper is the defaultAfter the insulation letter
RFlexible or soft stranded conductorAfter the insulation or sheath letter
KControl cableLeading letter
DJComputer and instrument cableLeading letters
PCopper wire braid screenAfter the sheath letter, or before it for pair screens
P2Copper tape screenAfter the sheath letter
P3Aluminium and plastic composite tape screenAfter the sheath letter
BFixed installation building wireLeading letter
2Double steel tape armour, or PVC outer sheath in the last positionArmour position or sheath position
3Fine steel wire armour, or PE outer sheath in the last positionArmour position or sheath position
4Thick steel wire armourArmour position
6Non-magnetic metal wire armour, used for single-core cablesArmour position

Block 1: insulation and conductor material

The insulation letter is the one that sets the thermal rating, and there are only a handful in common use. YJ means XLPE and gives a 90 °C continuous conductor temperature. V means PVC and gives 70 °C. Y means PE, which is chosen for its electrical properties in communication and medium voltage designs rather than for its temperature performance. That single first block tells you the two things that determine the ampacity: the insulation material, and the temperature it is allowed to reach.

The conductor letter follows immediately. Copper is the default and is normally omitted entirely: YJV is a copper cable. L after the insulation means aluminium, so YJLV is XLPE insulated with an aluminium conductor. Aluminium conductors are legitimate and widely used for large distribution feeders, but they have a higher resistivity, so an aluminium cable needs roughly two sizes more than a copper cable for the same current, and it needs termination compound and compatible lugs. Get this right in the RFQ, because YJV and YJLV differ only by one letter and by a great deal of money.

Block 2: the armour and sheath digits

The digits at the end of the code are read in pairs, and the second digit is the outer sheath material, not a second armour. The first digit is the armour: 2 is a double layer of galvanised steel tape, 3 is a layer of fine galvanised steel wire, 4 is a layer of thick steel wire, and 6 is a non-magnetic metallic armour used where the cable is single-core. The second digit is the outer sheath: 2 is PVC and 3 is polyethylene.

So YJV22 is steel tape armoured with a PVC sheath, and YJV23 is the same armour with a polyethylene sheath, which is the usual choice for aggressive or chemically contaminated soil and for direct burial where the sheath is exposed to moisture for decades. YJV32 is steel wire armoured with a PVC sheath and is the cable for vertical shafts and tensile loads. YJV62 is non-magnetic wire armoured with a PVC sheath, and it exists because magnetic armour around a single conductor heats up under alternating current. If there is no armour, there are no digits: YJV is unarmoured with a PVC sheath, YJY is unarmoured with a polyethylene sheath.

Armour and outer sheath digit combinations
Code endingArmourOuter sheathTypical use
noneNonePVCIndoor trays, conduit, dry internal routes
22Double steel tapePVCDirect burial, the general-purpose armoured cable
23Double steel tapePEBurial in aggressive soil, damp or chemically active ground
32Fine steel wirePVCVertical shafts, risers, long unsupported spans
33Fine steel wirePEWire armour in wet or aggressive ground
42Thick steel wirePVCHeavy tensile duty, river crossings, deep shafts
62Non-magnetic wirePVCSingle-core circuits where steel armour would heat

Block 3: the fire performance prefixes

These are written in front of the type code, and they are the part buyers most often get wrong, because several of them sound alike and mean quite different things. ZR is the general flame-retardant prefix. Where a class is specified it appears as ZA, ZB, ZC or ZD, the four flame-retardant classes of GB/T 19666, with ZA the most demanding and ZD the least; ZC is the common commercial grade.

WD means low smoke and halogen free, so WDZ is a low smoke zero halogen flame-retardant cable and WDZN adds fire resistance. NH alone means fire resistant without the low smoke requirement. Usefully, the prefixes tell you two separate things, and they are not the same thing at all: a flame-retardant cable resists the spread of fire along its own length, while a fire-resistant cable keeps working while it is burning. A cable that passes one test can fail the other, and life-safety circuits are where the distinction is tested.

  • ZR: flame retardant, general
  • ZA, ZB, ZC, ZD: flame-retardant classes A to D of GB/T 19666, most to least demanding
  • WD: low smoke, zero halogen; WDZ adds flame retardance
  • WDZN: low smoke, zero halogen, flame retardant and fire resistant
  • NH: fire resistant, for circuits that must survive a fire while operating
  • Flame retardant and fire resistant are two different tests on two different properties

Control cables: KVV, KVVP and their variants

The K prefix marks the family of control cables, which are built for 450/750 V and for many cores rather than for large cross-sections. The remaining letters follow the same rules as power cable: KVV is PVC insulated and PVC sheathed, KVV22 is the armoured version, and KVVR has flexible conductors for wiring between a machine and its control cabinet.

The screen letters matter here more than anywhere else, because control signals are small. KVVP has a copper wire braid screen over the laid-up cores, KVVP2 uses a copper tape screen instead, and KVVP22 combines a braid screen with steel tape armour for a route that needs both electrical screening and mechanical protection. A braid is flexible and makes a good low-frequency return path; a tape gives higher coverage at high frequency but is mechanically weaker and carries less fault current. Where the control cable runs alongside a variable speed drive output, the screened and armoured variants are worth the extra cost.

Common control cable codes
CodeConstructionWhere it is used
KVVPVC insulation, PVC sheath, 450/750 VGeneral control wiring in panels and machines
KVV22As KVV with double steel tape armourBuried or mechanically exposed control routes
KVVPAs KVV with a copper wire braid screenSignal circuits near interference sources
KVVP2As KVV with a copper tape screenHigh frequency screening where the cable does not move
KVVP22Braid screen plus steel tape armourInterference and mechanical risk together
KVVRFlexible conductors, PVC sheathWiring inside cabinets and between moving parts
KVVRPFlexible conductors with a braid screenFlexible screened control leads

Instrument and data cables: DJYPVP and the P letters

DJ marks the computer and instrument cable family, and the P letters inside it confuse everyone on first sight because their position changes their meaning. Read them in order: DJ is the family, the next letter is the insulation, then a P means the individual pairs are screened, then a letter for the sheath, then a final P for an overall screen. So DJYVP is polyethylene insulated with a PVC sheath and an overall braid screen, while DJYPVP is polyethylene insulated, individually screened pairs, PVC sheathed, with an additional overall braid screen.

The reason for two levels of screen is crosstalk. Individual pair screens stop one pair coupling into the next, and the overall screen stops external fields reaching the bundle. An analyser room or a plant with long 4-20 mA loops needs both. The tape equivalents follow the same pattern: DJYP2VP2 uses copper tape for both levels, and DJYP3VP3 uses an aluminium and plastic composite tape, which is cheaper and lighter but has a higher transfer impedance.

  • DJYVP: PE insulation, PVC sheath, overall braid screen
  • DJYPVP: individually screened pairs plus an overall braid screen
  • DJYP2VP2: as DJYPVP with copper tape screens
  • DJYP3VP3: as DJYPVP with aluminium and plastic composite tape screens
  • DJYPVP22: pair and overall screens plus steel tape armour
  • The final P is the overall screen; the P before the sheath letter screens the individual pairs

Reading the marking printed on the sheath

The printed marking on the sheath is the delivery note that cannot be lost. It carries the manufacturer, the full type code, the voltage rating, the number of cores and the cross-section, the standard, and the year of manufacture, and in most construction it also carries a sequential metre mark every metre along the length.

That metre mark is worth more than its size suggests. It is the only practical way to verify the length actually delivered on a drum, since a cable can otherwise only be measured by unwinding it or by weighing it. It is also the traceability link back to the production record, so if a drum is later found to be out of specification, the marking and the drum tag together identify exactly which production length it came from. Voltcore prints the brand, type, voltage, construction, standard and year with sequential metre marking, and supplies private label printing where the project requires it.

Anatomy of a sheath marking, decoded
Element of the markExampleWhat it tells you
ManufacturerVOLTCORETraceability back to the plant and the production record
Type codeYJV22XLPE, copper, steel tape armoured, PVC sheathed
Voltage rating0.6/1 kVU0/U: 600 V to earth, 1000 V between conductors
Construction4 × 95Four cores of 95 mm²
StandardGB/T 12706.1The standard it was designed and tested to
Concurrent standardIEC 60502-1Allows the cable to be checked against the IEC system
Conformity marksCE, CPR class or CCC as applicableThe regulatory approval held for the market
Year of manufacture2026Ageing evidence and warranty reference
Metre mark0123 mSequential length, used to verify the delivered quantity

European and North American cross-references

Projects built to IEC or NEC rules use different naming, and a buyer who receives a Chinese code and needs to match it to a local specification is doing a translation, not a comparison. There is no exact one-to-one mapping, because the families are defined in their own standards, but the equivalents below cover most enquiries. The electrical and mechanical properties are what must match; the name is only a label.

One caution on the North American side: listing is a property of a specific product under a specific file number, not of a type code. Where a project requires a listed construction, ask for the listing evidence for that product and check it against the register rather than accepting the type name alone.

Approximate cross-references between the naming systems
Chinese codeEuropean harmonised equivalentNorth American equivalent
VVN07VV-, PVC insulated and sheathedPVC power cable, 600 V
YJVN2XY, XLPE insulated PVC sheathedXHHW-2 single conductor, or type TC multicore
YJV22N2XRY with armour, or a directly equivalent armoured constructionMC cable or armoured cable per UL 1569
KVV / KVVPLiYY / LiYCY, unarmouredType PLTC or ITC control cable
BV, 450/750 VH07V-U / H07V-RTHHN or THWN-2 building wire
BVRH07V-K, flexibleStranded THHN
WDZ-YJYN2XH, LSZHLSZH constructions per the project specification

Frequently asked questions

What does YJV22 mean in full?

YJ is XLPE insulation, the missing conductor letter means copper, the first 2 is a double layer of galvanised steel tape armour, and the second 2 is a PVC outer sheath. Written as YJV22 0.6/1 kV 4 × 95 it is a four-core 95 mm² XLPE insulated, steel tape armoured, PVC sheathed cable rated 600 V to earth and 1000 V between conductors.

What is the difference between YJV23 and YJV32?

YJV23 has steel tape armour with a polyethylene outer sheath, and it is used for burial in damp or chemically aggressive soil. YJV32 has fine steel wire armour with a PVC sheath, and it is used where the cable is loaded in tension, such as vertical shafts and long unsupported spans. One change is the sheath, the other is the armour.

What does the L in YJLV stand for?

It means the conductor is aluminium rather than copper. An aluminium conductor has higher resistivity, so the same current needs roughly two standard sizes more than a copper cable, and it requires compatible lugs and jointing compound. YJLV is common on large distribution feeders where the weight and material cost saving outweighs the larger size.

Is ZR the same as flame retardant class C?

ZR is the general flame-retardant prefix; ZC is a specific class within GB/T 19666, alongside ZA, ZB and ZD. In commercial practice a ZR marking usually corresponds to the C class, but if the project specifies a class, write ZA, ZB, ZC or ZD explicitly in the RFQ so the requirement can be tested against it.

Why does my DJYPVP cable have two screens?

The P before the sheath letter means each pair is individually screened, which stops crosstalk between pairs, and the final P is an overall screen, which stops external fields entering the bundle. Long 4-20 mA loops and instrument runs in electrically noisy plant need both, which is why DJYPVP costs more than DJYVP.