XLPE Insulated Power Cable

Cross-linking converts polyethylene from a thermoplastic into a thermoset. Once the molecular chains are bonded into a three-dimensional network the insulation no longer softens an

Cross-linking converts polyethylene from a thermoplastic into a thermoset. Once the molecular chains are bonded into a three-dimensional network the insulation no longer softens and flows when the conductor is overloaded, and that single change lifts maximum continuous conductor temperature from 70 °C to 90 °C and short-circuit withstand from 160 °C to 250 °C for up to 5 s. In practical terms the same copper cross-section delivers 20-25 % more usable current than a PVC-insulated equivalent, which is why XLPE has displaced PVC across almost every new industrial distribution project where loads are expected to grow.

Voltcore produces the full 0.6/1 kV family to IEC 60502-1 and GB/T 12706.1 on equipment purchased for exactly this range: compacted Class 2 stranding, silane cross-linking towers with controlled humidity, and a triple-head line so screening can be added if an enquiry comes in for a higher voltage. Below you will find four builds: YJV with a PVC oversheath for ordinary tray and conduit work, YJY with a polyethylene oversheath for wet ducts and low-smoke areas, YJLV with aluminium conductors for long feeder runs where cost per amp matters more than bending radius, and N2XSY supplied to the German VDE letter code used in European and African tender documents.

4 constructions in XLPE Insulated Power Cable

YJV XLPE Insulated PVC Sheathed Power Cable

YJV-0.6-1kV

Copper conductor, XLPE insulation, PVC oversheath: the default 0.6/1 kV distribution build for indoor tray, conduit and duct routes.

  • Rated voltage U0/U (Um): 0.6/1 (1.2) kV
  • Conductor: Class 2 stranded compacted copper, IEC 60228
  • Core count: 1, 2, 3, 4, 5, 3+1, 3+2, 4+1
  • Cross-section range: 1.5 - 630 mm²
Specification →

YJY XLPE Insulated PE Sheathed Low Smoke Power Cable

YJY-0.6-1kV

A polyethylene oversheath instead of PVC: halogen-free, near-zero water transmission, and available as a tested LSZH construction.

  • Rated voltage U0/U (Um): 0.6/1 (1.2) kV
  • Conductor: Class 2 stranded compacted copper, IEC 60228
  • Core count: 1, 2, 3, 4, 5, 3+1, 3+2, 4+1
  • Cross-section range: 1.5 - 630 mm²
Specification →

YJLV Aluminium Conductor XLPE Power Cable

YJLV-0.6-1kV

All-aluminium conductor in the same XLPE build as YJV — around 55 % lighter per metre, for long runs where cost per amp decides.

  • Rated voltage U0/U (Um): 0.6/1 (1.2) kV
  • Conductor: Class 2 stranded aluminium or aluminium alloy 8030, IEC 60228
  • Core count: 1, 2, 3, 4, 5, 3+1, 3+2, 4+1
  • Cross-section range: 10 - 630 mm²
Specification →

N2XSY / N2XY IEC 60502-1 XLPE Power Cable

N2XSY-0.6-1kV

The VDE letter-code version of the same IEC 60502-1 build, quoted against European and African tender documents.

  • Rated voltage U0/U (Um): 0.6/1 (1.2) kV
  • Code without screen: N2XY, unscreened build
  • Code with screen: N2XSY, copper wire screen with counter-helix copper tape
  • Conductor: Class 2 stranded copper to EN 60228, circular or sector-shaped (rm/sm)
Specification →

YJV or YJY: choosing the oversheath rather than the insulation

Both types use identical XLPE insulation and identical conductors, so all electrical ratings are shared. The difference sits in the outermost layer. A PVC oversheath (ST1/ST2 compound) is flexible, self-extinguishing and cheap; a polyethylene oversheath is stiffer, much less permeable to water vapour, and halogen-free because the polymer contains no chlorine.

Specify YJY where the route is permanently wet — flooded duct banks, river crossings inside conduit, untreated cable basements — or where a polyethylene oversheath is demanded by the utility. Specify YJV everywhere the cable is pulled around many bends or sits on a dry indoor tray, and note that PE sheaths have higher friction and can score more easily during pulling, so increase pulling-shoe radii accordingly.

  • PVC sheath: flexible, flame-retardant, easier pull through tight routes
  • PE sheath: lower water transmission, halogen-free, stiffer to handle
  • Low smoke variant available as WDZ-YJY to IEC 61034 and IEC 60754

Reading an N2XSY designation letter by letter

European tenders rarely use GB codes, so a quotation request arriving as N2XSY deters suppliers who do not read the VDE letter sequence. In DIN VDE 0276-603 the initial N identifies a standard-conforming power cable, 2X is cross-linked polyethylene insulation, S is a metallic screen of copper wires with a counter-helix copper tape, and Y is a PVC outer sheath. The code therefore describes construction order: conductor, XLPE, screen, sheath.

The practical trap is that many buyers write N2XSY when they actually need unscreened 0.6/1 kV cable, which VDE writes as N2XY. Voltcore quotes both, flags the difference on our offer, and states the screened cross-section of copper wires in mm² so the earth-fault carrying capacity can be checked against the network's maximum fault level.

Why aluminium YJLV makes sense on long runs and not on short ones

On a 300 m feeder the conductor is typically half the cable cost, so switching to aluminium changes the tender materially. On a 30 m sub-board connection inside a factory the saving evaporates: the aluminium conductor needs the next size up, larger lugs and bimetallic terminations, and the installer spends more time per joint than the metal saved.

Set the crossover at roughly 80-120 m for low-voltage feeders, depending on local labour rates and whether the route is already excavated. Voltcore supplies the equivalence table with every aluminium quotation and pre-fits factory-crimped bimetallic lugs where the engineer asks for them, which removes the most common source of aluminium joint failures.

  • Typical substitution: 50 mm² copper becomes 70 mm² aluminium
  • Allow 1.5x the joint termination time compared with copper
  • Ask for the resistance comparison in ohm/km before accepting the substitution

Request pricing across XLPE Insulated Power Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or export@voltcorecable.com · WhatsApp

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.