ISO 9001 · ISO 14001 · ISO 45001 · CE CPR EN 50575 · TÜV (PV) · UL · SAA sales@cable-export-manufacture.com +86 139 0658 4505 Downloads

RE-2Y(St)Y-300/500V

RE-2Y(St)Y PiMF Instrumentation Cable — DIN VDE Designated

The European equivalent of the DJ range: PE pairs, static screen, DIN 47100 identification.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

RE-2Y(St)Y is the DIN VDE designation used on European projects for the construction that Chinese specifications call DJYVP. Reading it: 2Y is polyethylene core insulation, (St) is a collective static screen of laminated foil with a tinned drain wire, and the final Y is the PVC sheath. PiMF — pairs in metal foil — describes the same idea applied to each pair, and Voltcore supplies both the PiMF and the collective-screen version.

European panel builders usually specify it for two reasons beyond performance: the core colours follow the DIN 47100 sequence that their drawings and termination schedules already use, and the sheath is available in light blue for intrinsically safe circuits, which is the identification an Ex i installer expects to see. Voltcore holds both compounds and the colour sequence in stock at Yixing so the cable matches a European drawing without a re-engineering round.

Specification

RE-2Y(St)Y 300/500 V — Technical Specification
ItemValue
Rated voltage U0/U300/500 V
ConductorClass 2 stranded plain annealed copper to DIN VDE 0295 / IEC 60228
Number of pairs1 – 24 (PiMF: 2 – 24)
Cross-section range0.5 – 2.5 mm²
InsulationPolyethylene (2Y), dielectric constant ≈ 2.3
Screen(St) static screen: aluminium-laminated foil with tinned copper drain wire over the bundle or over each pair
SheathPVC (Y), grey RAL 7032 or black; light blue for intrinsically safe circuits
Core identificationDIN 47100 colour sequence
Mutual capacitance at 1 kHz≤ 60–85 pF/m
Max. continuous conductor temperature70 °C
Test voltage2 kV rms core to core, 1 kV rms core to screen, 5 min
Minimum bending radius10 × cable overall diameter (fixed installation)

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorStranded plain annealed copper, Class 2 to DIN VDE 0295 / IEC 60228
  2. 2. InsulationPolyethylene (2Y) extruded at 0.5–0.7 mm wall, coloured to the DIN 47100 sequence
  3. 3. Pair twistingTwo cores twisted together at a 40–65 mm lay length, varied between adjacent pairs
  4. 4. Screen(St) static screen of aluminium-laminated plastic foil applied over each pair or over the bundle, with a tinned copper drain wire in continuous contact
  5. 5. Lay-up and binderScreened pairs cabled in concentric layers with fillers and a plastic binder tape
  6. 6. SheathPVC (Y), grey RAL 7032 or black, 1.2–1.8 mm nominal; light blue for intrinsically safe circuits

Reference dimensions and weights

RE-2Y(St)Y 300/500 V — 4-pair dimensions and weight (reference figures)
Pairs × cross-section (mm²)Conductor structure (No./mm)Insulation thickness (mm)Pair lay length (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)Mutual capacitance at 1 kHz (pF/m)
4×2×0.57/0.300.54012.422536.0≤ 60
4×2×0.757/0.370.54513.829024.5≤ 65
4×2×1.07/0.430.65015.235518.1≤ 70
4×2×1.57/0.520.65516.945512.1≤ 75
4×2×2.57/0.680.76519.86407.41≤ 85

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Polyethylene (2Y) insulation holds mutual capacitance at ≤ 60–85 pF/m for long analogue and bus runs
  • Laminated foil static screen with a tinned drain wire, giving 100 % coverage without braid cost
  • DIN 47100 core colour sequence so the cable matches European termination schedules directly
  • Light blue sheath option identifying intrinsically safe circuits to IEC 60079-14 practice
  • 300/500 V rating with 2 kV rms core to core and 1 kV rms core to screen
  • Grey RAL 7032 sheath as standard for panel and rack installation
  • PiMF version available with the foil applied to each pair for mixed-signal cables

Typical applications

  • European process plant projects specified to DIN VDE designations
  • Intrinsically safe loops on chemical, pharma and offshore installations
  • Panel building and machine building for export into the EU
  • Analogue and digital signal runs in control rooms and analyser houses
  • Replacement and retrofit work on German-built plant where the drawing names RE-2Y(St)Y

Ordering options

  • PiMF construction with the foil screen on each pair
  • Copper wire braid screen in place of, or in addition to, the foil (St) screen
  • Light blue or LSZH sheath, with capacitance and inductance documented for Ex i calculations
  • Steel wire armoured variant for outdoor and buried installation
  • Class 5 fine-wire conductors for flexible panel connections

Standards manufactured to

  • DIN VDE 0816 (instrumentation cable construction)
  • DIN VDE 0295 / IEC 60228 (conductor)
  • DIN 47100 (core colour sequence)
  • IEC 60332-1-2 (flame propagation)
  • IEC 60079-14 (intrinsically safe installation practice)
  • RoHS and REACH compliant compounds

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for RE-2Y(St)Y PiMF Instrumentation Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

RE-2Y(St)Y PiMF Instrumentation Cable — frequently asked questions

What does RE-2Y(St)Y mean?

2Y is polyethylene core insulation, (St) is a collective static screen of laminated foil with a drain wire, and the final Y is a PVC sheath. The leading RE identifies the instrumentation cable family under the German designation system used alongside DIN VDE 0816.

Is a foil screen as good as a braid?

At high frequency, better — a continuous foil gives 100 % coverage with no apertures. At power frequency and at VFD carrier frequencies the braid wins, because the deciding factor there is the resistance of the shield path. For instrumentation signals, which are neither high current nor fast, the foil is the usual and cheaper answer.

Can I get this cable with DIN 47100 colours?

Yes. Voltcore stocks the DIN 47100 colour sequence for the RE-2Y(St)Y range, so pairs are identified by the colour combination European drawings already specify. Numbered tape or printed numbering is used above roughly 10 pairs.

Why is the sheath blue on some versions?

Light blue identifies an intrinsically safe circuit under IEC 60079-14 installation practice. It tells an installer that the cable is part of an energy-limited circuit and must not be grouped with non-IS circuits without separation.

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.