WDZN-YJY-0.6/1kV

WDZN-YJY Low Smoke Halogen Free Fire Resistant Cable

One cable for the two requirements that normally take two: circuit integrity and zero halogen.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

Hospitals, metro stations and tunnels ask for two things at once: the circuit must survive the fire, and the cable must not fill the escape route with acid smoke while it does. WDZN-YJY puts a mica barrier under the XLPE insulation and wraps the assembly in halogen-free bedding and sheath, so circuit integrity to GB/T 19216.21 at 750 °C for 90 minutes and low-smoke zero-halogen performance come from one construction instead of two cables in two trays.

The gain is procurement and installation simplicity: one drum type, one gland schedule, one cleat spacing and one test file. Voltcore supplies WDZN-YJY at 0.6/1 kV in one to five cores from 1.5 mm² to 300 mm², with steel tape armouring as WDZN-YJY23 for buried or outdoor sections of the same circuit, and with BS 6387 C/W/Z or EN 50200 PH90 submissions where the project names an English standard rather than a GB one.

Specification

WDZN-YJY 0.6/1 kV — Technical Specification
ItemValue
Rated voltage U0/U0.6/1 kV
ConductorClass 2 stranded plain copper, IEC 60228
Fire barrierTwo layers phlogopite mica tape per core, minimum 25% overlap
InsulationXLPE, 90 °C continuous, 250 °C short-circuit (≤ 5 s)
Bedding and fillerHalogen-free low-smoke compound with glass-fibre fill
SheathLSZH polyolefin, orange, black or grey
Circuit integrityGB/T 19216.21 at 750 °C for 90 min; BS 6387 C/W/Z and EN 50200 PH90 on request
Flame retardanceGB/T 19666 class A or B; IEC 60332-3-24 category C
Halogen and smokeIEC 60754-1 ≤ 5 mg/g; IEC 60754-2 pH ≥ 4.3; IEC 61034-2 ≥ 60% transmittance
Core count1, 2, 3, 4, 5, 3+1, 3+2, 4+1
Min bending radius15 × OD unarmoured, 12 × OD armoured

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorClass 2 stranded plain copper, IEC 60228
  2. 2. Fire barrierTwo layers phlogopite mica tape per core, minimum 25% overlap
  3. 3. InsulationXLPE, colour-coded, 90 °C continuous rating
  4. 4. Bedding and fillerHalogen-free low-smoke bedding compound with glass-fibre fill over the laid-up cores
  5. 5. Outer sheathLSZH thermoplastic polyolefin, orange, black or grey

Reference dimensions and weights

WDZN-YJY 0.6/1 kV — 4-core reference dimensions and weight
Nominal cross-section (mm²)Conductor structure (n × mm)Insulation thickness (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)
4 × 107 / 1.350.719.87001.83
4 × 167 / 1.700.722.610301.15
4 × 257 / 2.140.926.815600.727
4 × 357 / 2.520.930.020700.524
4 × 5019 / 1.781.034.628300.387
4 × 7019 / 2.141.139.238600.268
4 × 9519 / 2.521.144.050800.193
4 × 12037 / 2.031.248.863000.153
4 × 15037 / 2.251.454.278000.124

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Mica barrier under the XLPE holds the circuit at 750 °C for 90 minutes to GB/T 19216.21 with rated voltage applied.
  • Halogen-free sheath releases not more than 5 mg/g acid gas to IEC 60754-1, keeping switchgear and electronics recoverable after a fire.
  • Smoke transmittance not below 60% to IEC 61034-2, roughly three times the visibility left by a PVC-sheathed fire cable.
  • 90 °C continuous and 250 °C short-circuit ratings mean no ampacity derating against standard XLPE cable.
  • Flame retardance to GB/T 19666 class A or B and IEC 60332-3-24 category C covers long bunched vertical runs.
  • Class 2 copper gives 1.83 Ω/km at 10 mm² falling to 0.124 Ω/km at 150 mm², so voltage drop can be checked on long hospital risers.
  • Armoured WDZN-YJY23 covers the outdoor and buried sections of the same essential circuit.

Typical applications

  • Hospital operating theatre, intensive care and essential-services distribution
  • Metro and rail station emergency lighting and smoke control circuits
  • Road and rail tunnel ventilation and evacuation systems
  • Airport terminal fire pump and emergency power feeders
  • High-rise residential escape corridor and stairwell pressurisation fans
  • Plant safe-shutdown circuits with a zero-halogen requirement

Ordering options

  • WDZN-YJY23 — steel tape armoured for buried and outdoor sections
  • EN 50200 PH90 or PH120 submission with Annex E water spray
  • Tinned copper conductor for damp tunnels and coastal projects
  • Orange sheath printed EMERGENCY or FIRE to match identification schedules
  • Floor-by-floor cut lengths with tags and pre-fitted glands

Standards manufactured to

  • GB/T 19216.21
  • IEC 60331-21
  • BS 6387 (C/W/Z on request)
  • BS 8491
  • EN 50200
  • GB/T 19666
  • IEC 60502-1
  • IEC 60754-1
  • IEC 60754-2
  • IEC 61034-2

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for WDZN-YJY LSZH Fire Resistant Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

WDZN-YJY LSZH Fire Resistant Cable — frequently asked questions

Does a halogen-free sheath reduce fire resistance compared with PVC?

No. Circuit integrity comes from the mica barrier under the insulation; the sheath burns away in both cases within the first minutes of flame contact. Halogen-free changes what is released while that happens — less acid gas, more visibility — so it improves the outcome for people and equipment without altering the integrity test result.

What is the difference between WDZ-YJY and WDZN-YJY?

The N stands for fire resistant. WDZN-YJY adds two layers of mica tape to each conductor and is submitted to a circuit-integrity test with voltage applied during the fire. WDZ-YJY is halogen-free and flame retardant only, tested for flame spread and smoke. The two look similar on a drum, so check the datasheet standard rather than the sheath colour.

Can a fire pump feeder and escape lighting share one cable schedule?

Yes if the core count and cross-section suit both, which is uncommon: a pump feeder is usually 25 mm² or larger while lighting circuits are 4 mm² or less. Buying them on one order makes sense for the test file and drum labelling, but size them separately and keep pump circuits on their own cores so a lighting fault cannot trip the pump.

Is WDZN-YJY suitable for tunnels that are washed down?

Yes, using the armoured WDZN-YJY23 with sealed glands. The mica barrier is not hygroscopic, unlike the magnesium oxide in rigid MI cable, so water at a cut end does not destroy insulation resistance along the length. For permanently wet sections, specify tinned conductors and gel-filled or heat-shrink terminations.

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.