ZH-BYJ-450/750V

HFFR / ZH Series Halogen Free Flame Retardant Building Cable

Single-core building wire and 0.6/1 kV power cable on one halogen-free compound platform.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

The ZH series covers the everyday wiring layer of a building: 450/750 V single-core wire for conduit and trunking, and 0.6/1 kV multi-core cable for sub-mains. Insulation is cross-linked polyolefin rather than PVC, rated 90 °C continuous with a 125 °C grade for hot ceiling voids and luminaire drops, and the sheath is a halogen-free flame-retardant compound that clears IEC 60332-1 on a single sample and IEC 60332-3 when bunched.

Conductor form decides how the wire installs. Voltcore supplies Class 1 solid for conduit work where the wire is pushed through, and Class 2 or Class 5 stranded where it is pulled around bends or terminated into spring-cage terminals. Sizes run from 1.5 mm² to 630 mm² in the same colour set as PVC building wire, so an existing lighting and power schedule transfers across without re-approval when a project moves to halogen-free.

Specification

ZH series 450/750 V and 0.6/1 kV — Technical Specification
ItemValue
Rated voltage U0/U450/750 V single-core; 0.6/1 kV multi-core
ConductorPlain copper, Class 1 solid, Class 2 or Class 5 stranded, IEC 60228
InsulationCross-linked polyolefin, 90 °C standard, 125 °C high-temperature grade
Sheath (multi-core)Halogen-free flame-retardant polyolefin, white, grey or black
Flame retardanceIEC 60332-1 single cable; IEC 60332-3-24 category C bunched; GB/T 19666 class B or C
Halogen acid gasIEC 60754-1, not more than 5 mg/g
Smoke densityIEC 61034-2, light transmittance not below 60%
Cross-section range1.5 – 630 mm²
Core count1 to 5 cores, plus 3+1, 3+2 and 4+1 arrangements
Min bending radius6 × OD single-core, 15 × OD multi-core
Installation temperatureNot below 0 °C without pre-heating

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorPlain copper, Class 1 solid for conduit work or Class 2 / Class 5 stranded for pulling
  2. 2. InsulationCross-linked polyolefin, 90 °C standard or 125 °C high-temperature grade, colour-coded
  3. 3. Filler and bedding (multi-core)Halogen-free filler with a low-smoke binder tape over the laid-up cores
  4. 4. Outer sheath (multi-core)HFFR polyolefin, white, grey or black, flame retardant to IEC 60332-3-24

Reference dimensions and weights

ZH-BYJ 450/750 V — single-core reference dimensions and weight
Nominal cross-section (mm²)Conductor structure (n × mm)Insulation thickness (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)
1.51 / 1.380.72.82012.1
2.51 / 1.780.83.4317.41
41 / 2.250.83.9464.61
61 / 2.760.84.4663.08
107 / 1.351.06.11121.83
167 / 1.701.07.11721.15
257 / 2.141.28.82650.727
357 / 2.521.210.03650.524
5019 / 1.781.411.75200.387
7019 / 2.141.413.47200.268

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Cross-linked polyolefin insulation rated 90 °C, with a 125 °C grade for luminaire drops and hot ceiling voids.
  • Halogen-free compound gives not more than 5 mg/g acid gas to IEC 60754-1 and pH not below 4.3 to IEC 60754-2.
  • Single-core wire clears IEC 60332-1 with char length well inside the 50 mm limit measured from the lower edge of the sample.
  • Same colour set and size range as PVC building wire, so a lighting and power schedule transfers without re-approval.
  • Class 1 solid conductors push cleanly through conduit; Class 5 stranded suits spring-cage terminals and tight bends.
  • Smoke output well below PVC to IEC 61034-2, which decides the specification in wards, classrooms and corridors.
  • Insulation resistance at 90 °C sits an order of magnitude above the minimum, giving margin on long final circuits.

Typical applications

  • Lighting and small power final circuits in hospitals, schools and hotels
  • Conduit and trunking wiring in high-rise residential towers
  • Luminaire and emergency fitting drops where ceiling voids run hot
  • Sub-mains from floor distribution boards to tenant panels
  • Public buildings operating a declared halogen-free wiring policy
  • Refurbishment projects replacing PVC wire to meet current fire-safety rules

Ordering options

  • Class 5 flexible conductor for tray and equipment wiring
  • 125 °C high-temperature insulation grade
  • 0.6/1 kV multi-core ZH-YJV equivalent with HFFR sheath
  • White, grey, black or custom RAL sheath colours with printed legends
  • 100 m coils, 500 m drums and cut-to-length with metre marking

Standards manufactured to

  • JB/T 10491
  • GB/T 19666
  • IEC 60332-1
  • IEC 60332-3-24
  • IEC 60754-1
  • IEC 60754-2
  • IEC 61034-2
  • IEC 60228

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for HFFR / ZH Halogen Free Building Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

HFFR / ZH Halogen Free Building Cable — frequently asked questions

Is ZH the same marking as WDZ?

Both point at halogen-free flame-retardant compounds, but they are used differently. ZH is the marking for building wire and cable under the flame-retardant series; WDZ adds the explicit low-smoke declaration and is used on power cable. Confirm the test standard cited on the datasheet — IEC 60754-1 for acid gas, IEC 61034-2 for smoke — rather than relying on the prefix.

Can ZH-BYJ share a conduit with existing PVC wire?

Physically yes: outside diameters match PVC wire within normal tolerance, so conduit fill is unchanged. Electrically, each circuit keeps its own conductor temperature rating, so the 70 °C PVC circuits and the 90 °C XLPO circuits are rated separately. Apply the normal grouping derating for the number of circuits in the conduit, and check the total fill against the wiring rules.

Does the halogen-free insulation tolerate termination heat?

Cross-linked polyolefin does not melt like PVC, so ferrule crimping and normal termination practice are unaffected, and the 90 °C or 125 °C rating covers hot accessories. Avoid direct flame or prolonged contact with a soldering iron, since the compound will char rather than flow. No special tools are needed beyond those used for XLPE cable.

What bending radius applies to 1.5 mm² and 2.5 mm² wire?

Six times overall diameter, which is about 17 mm at 1.5 mm² and 20 mm at 2.5 mm². In practice the conduit bend radius governs, and conduit is rarely bent tighter than that. The figure matters for tray and back-box work, where a tighter loop can leave the insulation under permanent stress at the terminal.

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.