LSZH-PH90-300/500V

LSZH Fire Alarm & Emergency Lighting Cable to EN 50575 Euroclass

Euroclass reaction-to-fire and EN 50200 circuit integrity from the same halogen-free build.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

Two separate requirements meet in a fire alarm or emergency lighting cable. EN 50575 governs reaction to fire for cable placed on the EU market: the Euroclass — Dca-s2,d2,a1 for general installation, Cca-s1,d1,a1 for hospitals and transport hubs, B2ca-s1,d1,a1 for the highest-risk escape routes — with smoke, flaming droplet and acidity suffixes declared alongside. EN 50200 governs whether the circuit still works during the fire, graded PH30, PH60, PH90 or PH120.

Voltcore builds this cable at 300/500 V in 1.0, 1.5, 2.5 and 4 mm² with two to four cores, each core mica-taped before insulation so the PH rating is earned per conductor rather than across the bundle. An aluminium-polyester screen with a tinned drain wire is standard for loops running beside power cable. Sheath colours follow the usual red for fire alarm and white or orange for emergency lighting, and every drum ships with the declaration of performance.

Specification

LSZH fire alarm and emergency lighting cable 300/500 V — Technical Specification
ItemValue
Rated voltage U0/U300/500 V
ConductorPlain copper, Class 1 solid or Class 2 stranded, IEC 60228
Fire barrierMica glass composite tape per core, minimum 25% overlap
InsulationHalogen-free cross-linked polyolefin, 90 °C
ScreenAluminium-polyester tape with 0.5 mm² tinned copper drain wire (optional)
SheathLSZH polyolefin, red, white or orange
CPR EuroclassDca-s2,d2,a1; Cca-s1,d1,a1; B2ca-s1,d1,a1 to EN 50575
Circuit integrityEN 50200 PH30 / PH60 / PH90 / PH120, Annex E water spray on request
Smoke and acidityIEC 61034-2 ≥ 60% transmittance; IEC 60754-1 ≤ 5 mg/g; acidity class a1
Core count and sizes2, 3, 4 cores in 1.0, 1.5, 2.5, 4 mm²
Min bending radius6 × OD fixed, 10 × OD where routed through inspection bends

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorPlain copper, Class 1 solid or Class 2 stranded, IEC 60228
  2. 2. Fire barrierMica glass composite tape applied per core at minimum 25% overlap
  3. 3. InsulationHalogen-free cross-linked polyolefin, colour-coded, 90 °C rating
  4. 4. ScreenAluminium-polyester tape with a 0.5 mm² tinned copper drain wire (optional on dedicated routes)
  5. 5. Outer sheathLSZH polyolefin, red for fire alarm, white or orange for emergency lighting

Reference dimensions and weights

LSZH fire alarm cable 300/500 V — 2-core screened reference dimensions and weight
Nominal cross-section (mm²)Conductor structure (n × mm)Insulation thickness (mm)ScreenApprox. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)
2 × 1.01 / 1.130.6Al/PET tape + 0.5 mm² drain wire8.310518.1
2 × 1.51 / 1.380.7Al/PET tape + 0.5 mm² drain wire10.415012.1
2 × 2.51 / 1.780.8Al/PET tape + 0.5 mm² drain wire11.21807.41
2 × 41 / 2.250.8Al/PET tape + 0.5 mm² drain wire12.32354.61
2 × 61 / 2.760.8Al/PET tape + 0.5 mm² drain wire13.43003.08
2 × 107 / 1.351.0Al/PET tape + 0.5 mm² drain wire16.44501.83
2 × 167 / 1.701.0Al/PET tape + 0.5 mm² drain wire18.86201.15
2 × 257 / 2.141.2Al/PET tape + 0.5 mm² drain wire22.09000.727

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Euroclass declared to EN 50575 in Dca-s2,d2,a1, Cca-s1,d1,a1 or B2ca-s1,d1,a1 with a declaration of performance per batch.
  • Circuit integrity graded PH30, PH60, PH90 or PH120 to EN 50200, with Annex E water spray where the specification asks for it.
  • Mica tape is applied to each core individually, so a fault on one leg cannot short the loop to earth during the test.
  • Aluminium-polyester screen with a 0.5 mm² tinned drain wire holds loop immunity on addressable systems beside power cable.
  • Acidity class a1: conductivity below 2.5 µS/mm and pH above 4.3 to IEC 60754-2, protecting detectors and panels after exposure.
  • Smoke transmittance not below 60% to IEC 61034-2, keeping escape signage visible through the evacuation period.
  • 300/500 V rating across 1.0 to 25 mm² lets the designer solve voltage drop on long loops rather than accept 1.5 mm² everywhere.

Typical applications

  • Addressable and conventional fire detection loops
  • Emergency and escape lighting circuits in commercial and public buildings
  • Fire alarm sounder and voice evacuation circuits
  • Smoke damper, fire shutter and door-holder control wiring
  • Sprinkler flow switch and alarm valve monitoring circuits
  • Hospital, airport and metro station life-safety systems

Ordering options

  • Unscreened version where the loop runs in a dedicated fire-resistant compartment
  • Class 5 stranded conductor for flexible connections into detectors and sounders
  • Overall tinned copper braid screen for high electromagnetic interference areas
  • Red, white, orange or violet sheath printed FIRE ALARM with metre marking
  • 300 m and 500 m drums, or pre-cut loop lengths per zone with tags

Standards manufactured to

  • EN 50575
  • EN 50200
  • BS 8434-2
  • IEC 60754-1
  • IEC 60754-2
  • IEC 61034-2
  • IEC 60332-1
  • IEC 60332-3-24
  • IEC 60228

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for LSZH Fire Alarm & Emergency Lighting Cable to EN 50575

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

LSZH Fire Alarm & Emergency Lighting Cable to EN 50575 — frequently asked questions

What is the difference between the Euroclass and the PH rating?

They measure different things. The EN 50575 Euroclass covers reaction to fire — how much heat and smoke the cable contributes and whether it drips flaming particles. The EN 50200 PH rating covers circuit integrity — whether the cable still carries the signal while burning. A cable can be B2ca-s1,d1,a1 and carry no PH rating at all, which is fine for a general circuit and wrong for a fire alarm loop.

Which Euroclass do I need for a hospital or metro project?

Cca-s1,d1,a1 is the common requirement for hospitals, schools and transport hubs, with B2ca-s1,d1,a1 reserved for escape routes and high-risk areas. Dca-s2,d2,a1 is the minimum normally accepted for general installation in the EU. Confirm against the local building code, since several countries set a higher floor than the CPR minimum for public buildings.

Can fire alarm cable share a tray with power cable?

Only with segregation to the wiring rules, typically 300 mm separation or a screened cable plus a compartmented tray. Specify the screened version and keep the drain wire earthed at the panel end only, to avoid earth loops. Where the shared route is not fire segregated, the alarm cable must also carry the circuit-integrity rating for that section.

Do you issue a declaration of performance and CE marking?

Yes. Voltcore holds CE certification to CPR EN 50575 and issues a declaration of performance naming the Euroclass, the intended use and the assessment route for the class. State the class you need at RFQ stage, because the compound and the notified-body involvement differ between Dca, Cca and B2ca submissions.

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.