WDZ-BYJ-450/750V

WDZ-BYJ Halogen-Free Building Wire, 450/750 V

Cross-linked halogen-free insulation in the 450/750 V building wire sizes, for the buildings where the smoke matters.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

The BYJ part of the name is the insulator: a cross-linked polyolefin instead of PVC. Cross-linking changes the thermal picture entirely, because the compound no longer softens and flows when it is heated. A PVC/C wire is rated 70 °C continuous; a BYJ wire is rated 90 °C and holds 250 °C on short circuit, which is the same temperature a power cable insulation reaches.

The WDZ prefix is the fire performance: low smoke, zero halogen, and low toxicity. When a PVC wire burns it releases hydrogen chloride, which corrodes the equipment in the room and attacks the escape route. A halogen-free compound does not. That is why the specification changes by building type, and why a metro station, a hospital or a data centre specifies WDZ-BYJ where a house is wired in PVC.

Specification

WDZ-BYJ 450/750 V — technical specification
ItemValue
Rated voltage U0/U450/750 V
ConductorClass 1 solid to 6 mm², Class 2 stranded from 10 mm², IEC 60228
Cross-section range1.5 – 185 mm²
InsulationIrradiated cross-linked halogen-free polyolefin, 0.7–1.6 mm nominal
Maximum conductor temperature+90 °C continuous
Short-circuit temperature250 °C for 5 s
Minimum installation temperature−15 °C
Smoke behaviourLow smoke to IEC 61034-2, light transmittance above 60%
Acidity and toxicityHalogen-free to IEC 60754, low toxicity
Flame behaviourIEC 60332-3-24 for bunched wiring
StandardGB/T 19666, JB/T 10491
Supply form100 m coils as standard, or drums for the larger sizes

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorClass 1 solid annealed copper up to 6 mm²; Class 2 stranded from 10 mm², to IEC 60228
  2. 2. InsulationIrradiated cross-linked halogen-free polyolefin, 0.7–1.6 mm nominal wall, coloured
  3. 3. Surface and markingSmooth finish with printed marking at intervals: GB/T 19666, WDZ-BYJ, size, voltage rating
  4. 4. PackageSupplied in 100 m coils, shrink-wrapped and labelled; drums for 25 mm² and above

Reference dimensions and weights

WDZ-BYJ 450/750 V — reference dimensions, weight, resistance and current rating
Nominal cross-section (mm²)Conductor structure (n×mm)Insulation thickness (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)Current rating in conduit at 30 °C (A)
1.51 × 1.380.72.92112.118
2.51 × 1.780.83.5327.4125
41 × 2.250.84.0464.6133
61 × 2.760.84.5643.0843
107 × 1.351.06.01121.8359
167 × 1.701.07.11651.1580
257 × 2.141.28.82570.727105
357 × 2.521.210.03470.524131

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Irradiated cross-linked insulation rated 90 °C continuous, against 70 °C for a PVC/C building wire.
  • Short-circuit rating of 250 °C for 5 s, the same figure a cross-linked power cable carries.
  • Halogen-free compound with no hydrogen chloride released when it burns, to IEC 60754.
  • Low smoke to IEC 61034-2, with light transmittance above 60% in the smoke chamber test.
  • Bunched wiring flame performance to IEC 60332-3-24, which is the test a vertical shaft demands.
  • Current ratings higher than PVC wire of the same size, because the 90 °C rating permits more current.
  • 450/750 V rating to GB/T 19666, in the same sizes and colours as a standard building wire.

Typical applications

  • Hospitals, clinics and healthcare buildings
  • Metro stations, tunnels and enclosed public transport buildings
  • Data centres and telecommunications rooms
  • Schools, theatres and enclosed assembly buildings
  • High-rise residential escape routes and stairwells
  • Commercial towers with a specified fire strategy

Ordering options

  • 1.5–185 mm² in 100 m coils or on drums
  • Solid Class 1 up to 6 mm², Class 2 stranded from 10 mm²
  • Full colour range including green-yellow
  • Flame-retardant and higher fire-performance grades on request
  • Private-label coil labels and OEM printing

Standards manufactured to

  • GB/T 19666
  • JB/T 10491
  • IEC 60332-3-24
  • IEC 61034-2
  • IEC 60754
  • IEC 60228

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for WDZ-BYJ Halogen-Free Building Wire

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

WDZ-BYJ Halogen-Free Building Wire — frequently asked questions

When is WDZ-BYJ required rather than BV?

When the fire strategy says so. It is the specification for buildings with enclosed escape routes or with equipment that must survive a fire: hospitals, metro stations, data centres, theatres and high-rise stairwells. In a house or a light commercial unit, PVC-insulated BV is correct and more economical, and no code requires the halogen-free compound.

Why is the current rating higher than for BV?

Because of the temperature class. A PVC/C wire is rated 70 °C continuous; a cross-linked BYJ wire is rated 90 °C. The same 2.5 mm² conductor can carry more current before the insulation reaches its limit. Use the 90 °C column of the current rating table, and derate for grouping in the same way as you would for a PVC wire.

What does the WDZ prefix mean?

It is the Chinese fire-performance code: W for low smoke, D for low toxicity, and Z for flame retardant. Together they say the compound is halogen-free, gives off little smoke when it burns, and resists the spread of flame. The tests behind them are IEC 61034-2 for the smoke, IEC 60754 for the halogen content, and IEC 60332-3-24 for the flame spread on bunched wiring.

Is it harder to strip and terminate?

Slightly. Cross-linked insulation is tougher than PVC, so a worn stripping tool will leave a ragged edge. A sharp automatic stripper handles it without a problem, and the payoff at the termination is a conductor that will not creep under a screw, because the insulation does not soften at the temperatures a loaded terminal reaches.