MVV-0.66/1.14kV

MVV / MVV22 PVC Insulated Mining Power Cable to MT 818

Fixed-installation mine power cable with the earth core sized by MT 818 rather than by guesswork.

  • Lead time15–25 working days
  • Minimum500 m per size
  • SampleFree up to 5 m
Illustrative cross section. Construction layers listed below.

MVV is the fixed-installation power cable of a coal mine: feeder runs along roadways, connections to section substations, and supplies to pumps and ventilation fans underground. It is PVC insulated and sheathed at 0.66/1.14 kV, built in 3+1, 3+2 and 4-core arrangements where the earth core is not an afterthought but a sized conductor set by MT 818. MVV22 adds double steel tape armour where the route is exposed to roof fall, passing machinery or burial in the mine floor.

Underground conditions shape the construction. The sheath must pass the MT 386 flame and antistatic test, the cable is cleated along rib sides where it can be struck, and the route is often damp and acidic. Voltcore builds MVV with a Class 5 flexible conductor rather than Class 2, so jointing in a confined roadway is practical, and marks each drum with the MT 818 part reference, voltage grade and metre marking that a mine inspection regime asks to see.

Specification

MVV / MVV22 0.66/1.14 kV — Technical Specification
ItemValue
Rated voltage U0/U0.66/1.14 kV (0.38/0.66 kV and 1.9/3.3 kV on request)
ConductorFlexible plain copper, Class 5 stranded, IEC 60228
InsulationPVC type A, 70 °C conductor rating
Core arrangement3+1, 3+2 and 4 cores; earth core sized per MT 818
BeddingPVC or halogen-free bedding compound
Armour (MVV22)Double galvanised steel tape, 0.2 – 0.5 mm
SheathPVC, flame retardant and antistatic to MT 386
Flame and antistaticMT 386 — bunched flame test with surface resistance measurement
Cross-section range4 – 400 mm² (3+1 typically 4 – 300 mm²)
Min bending radius6 × OD for MVV, 12 × OD for MVV22
Installation temperatureNot below 0 °C without pre-heating

Layer-by-layer construction

Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.

  1. 1. ConductorClass 5 flexible stranded plain copper, IEC 60228; earth core sized per MT 818
  2. 2. InsulationPVC type A, colour-coded, 70 °C conductor rating
  3. 3. Filler and binderNon-hygroscopic filler with a binder tape over the laid-up cores
  4. 4. BeddingExtruded PVC or halogen-free bedding under the armour
  5. 5. Armour (MVV22)Double galvanised steel tape, 0.2 – 0.5 mm, applied with a gap
  6. 6. Outer sheathPVC, flame retardant and antistatic to MT 386, black

Reference dimensions and weights

MVV 0.66/1.14 kV — 3+1 core reference dimensions and weight
Nominal cross-section (mm²)Conductor structure (n × mm)Insulation thickness (mm)Sheath thickness (mm)Approx. overall diameter (mm)Approx. weight (kg/km)Max. DC resistance at 20 °C (Ω/km)
3 × 4 + 1 × 456 / 0.301.42.421.56204.95
3 × 6 + 1 × 684 / 0.301.42.623.47903.30
3 × 10 + 1 × 1084 / 0.401.62.827.211601.91
3 × 16 + 1 × 16126 / 0.401.63.030.616601.21
3 × 25 + 1 × 16196 / 0.401.83.235.222900.780
3 × 35 + 1 × 16276 / 0.401.83.438.429200.554
3 × 50 + 1 × 25396 / 0.402.03.643.639100.386
3 × 70 + 1 × 35360 / 0.502.03.848.852100.272
3 × 95 + 1 × 50475 / 0.502.24.054.669000.206

Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.

Engineering characteristics

  • Class 5 flexible conductor and 6 × OD bending radius make jointing practical in a roadway with limited working space.
  • Earth and monitoring cores sized by MT 818 rather than matched to the phase, keeping fault-loop impedance inside the mine's protection settings.
  • PVC sheath compounded to pass MT 386: bunched flame propagation plus the antistatic surface resistance requirement for gassy atmospheres.
  • MVV22 double steel tape armour resists roof fall debris, impact from passing machinery and crushing at floor level.
  • 70 °C conductor rating with insulation thickness stepped from 1.4 mm to 2.2 mm across the range, giving margin on 1.14 kV circuits.
  • Core identification and printed metre marking follow the inspection schedule, so remaining drum length can be recorded at the face.
  • Halogen-free bedding and sheath option for escapeways and intake airways where smoke matters.

Typical applications

  • Underground roadway feeder cables from section substations
  • Main pump, drainage and dewatering supplies
  • Ventilation and auxiliary fan power circuits
  • Belt conveyor, hoist and crusher supplies underground
  • Pit head surface plant and coal preparation plant distribution
  • Armoured runs across roadways and along the mine floor

Ordering options

  • MVV22 — double steel tape armoured for exposed and floor-level routes
  • MVV32 and MVV42 — steel wire armoured for shafts and vertical runs
  • 0.38/0.66 kV and 1.9/3.3 kV voltage grades
  • Halogen-free sheath version for escapeways and intake airways
  • Cut-to-length drum sets tagged per roadway and section

Standards manufactured to

  • MT 818
  • MT 386
  • GB/T 12706.1
  • IEC 60228

Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.

Price and availability for MVV / MVV22 Mining Power Cable

Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.

  • Engineer-reviewed before pricing
  • Reference drawings issued with the quotation
  • Free sample up to free sample up to 5 m

or sales@cable-export-manufacture.com · WhatsApp

MVV / MVV22 Mining Power Cable — frequently asked questions

What does MT 818 cover, and will it satisfy an overseas mine?

MT 818 is the Chinese coal industry series covering mining cable by type and voltage grade: construction, dimensions, tests and core arrangements, with MT 386 for flame and antistatic behaviour. Overseas mines often need their own national approval. Voltcore supplies the full MT 818 test file, dimensions and compound identification so the mine's engineer or a local approving body can assess the construction directly.

Why is the earth core smaller than the phase cores?

MT 818 sizes the earth core for the fault current it must carry for the clearing time of the protection, not to match the phase. At 3 × 25 + 1 × 16 the earth is 16 mm² because that is what the fault-loop calculation requires. Specifying an equal earth core adds weight and cost without improving the trip, unless a longer face or a different protection setting demands it.

Can MVV be used on a moving machine?

No. MVV is a fixed-installation cable cleated along a roadway or buried in the floor. A machine that moves — shearer, roadheader, shuttle car — needs a rubber-sheathed flexible trailing cable such as MY, MYP or MCP, whose conductor stranding, insulation and sheath are designed for repeated flexing and dragging.

What bending radius applies, and can it be installed in cold conditions?

Six times overall diameter for MVV and twelve times for the armoured MVV22. Installation should not be attempted below 0 °C without pre-heating the drum, because PVC stiffens and a cold bend can crack the sheath. For shaft work in winter, Voltcore can supply a low-temperature sheath grade rated for installation down to -10 °C.

Tell us the load, the route and the standard — we will come back with a sized quotation

RFQs are answered by an application engineer first. Typical reply within 12 hours, CST working days.