RTD-PT100-3/4W
Pt100 RTD Signal Cable — 3-Wire and 4-Wire Screened Construction
Screened triples and quads that keep lead resistance out of the temperature reading.
A Pt100 is a resistor, nominally 100 Ω at 0 °C and changing by 0.385 Ω per kelvin to IEC 60751. That sensitivity is what makes it accurate and what makes it vulnerable: the instrument cannot distinguish resistance in the sensor from resistance in the copper that reaches it, so 1 Ω of lead resistance reads as 2.6 °C. The third and fourth wires are the industry's answer.
Voltcore builds this cable as a screened twisted triple or quad rather than as a multi-core, because the cancellation a three-wire circuit depends on requires all three conductors to be identical in length, cross-section and termination. Cores are twisted together with a short lay length so they share the same route and the same temperature, then screened with foil and braid — the signal is only 100 mV or so across the sensor at typical excitation currents.
Specification
| Item | Value |
|---|---|
| Sensor type | Pt100 to IEC 60751, α = 0.00385 Ω/Ω/°C |
| Connection | 3-wire (compensated) or 4-wire (Kelvin) |
| Conductor | Class 5 flexible plain annealed copper, IEC 60228 |
| Cross-section range | 0.5 – 2.5 mm² |
| Construction | 3-core or 4-core twisted, laid up as one triple or quad |
| Insulation | PVC or polyethylene |
| Screen | Aluminium foil plus tinned copper braid ≥ 85 % coverage, with tinned drain wire |
| Sheath | PVC grey or black; LSZH and blue Ex i variants available |
| Max. continuous conductor temperature | 70 °C |
| Test voltage | 2 kV rms core to core, 1 kV rms core to screen, 5 min |
| Minimum bending radius | 10 × cable overall diameter |
| Core identification | Three red cores for 3-wire; colour-coded pairs for 4-wire |
Layer-by-layer construction
Listed from the conductor outward. Read this alongside the specification table — the two together tell you whether the cable will survive its installation method.
- 1. ConductorBunched fine-wire plain annealed copper, Class 5 to IEC 60228, identical construction in every core
- 2. InsulationPVC or polyethylene extruded at 0.5–0.7 mm wall, colour coded for polarity identification
- 3. TwistingThree or four cores twisted together at a short lay length so all leads follow the same route and temperature
- 4. Foil screenAluminium-laminated polyester foil applied with overlap, 100 % coverage, with a tinned drain wire
- 5. Braid screenTinned copper wire braid at ≥ 85 % coverage over the foil
- 6. SheathPVC grey or black, 1.0–1.5 mm nominal; LSZH and light blue Ex i variants available
Reference dimensions and weights
| Cores × cross-section (mm²) | Conductor structure (No./mm) | Insulation thickness (mm) | Approx. overall diameter (mm) | Approx. weight (kg/km) | Lead resistance per conductor at 100 m (Ω) | Approximate 2-wire measurement error at 100 m (°C) |
|---|---|---|---|---|---|---|
| 4×0.5 | 16/0.20 | 0.5 | 7.2 | 95 | 3.90 | 20.3 |
| 4×0.75 | 24/0.20 | 0.5 | 7.8 | 120 | 2.60 | 13.5 |
| 4×1.0 | 32/0.20 | 0.6 | 8.6 | 150 | 1.95 | 10.1 |
| 4×1.5 | 30/0.25 | 0.6 | 9.4 | 195 | 1.33 | 6.9 |
| 4×2.5 | 50/0.25 | 0.7 | 11.0 | 280 | 0.80 | 4.2 |
Reference figures for preliminary sizing and drum planning. Overall diameter and weight vary with strand construction and sheath thickness tolerance; certified drawings are issued with each quotation.
Engineering characteristics
- Cores built to identical construction, which is what the three-wire cancellation assumes
- 0.385 Ω/K sensitivity means 1 Ω of lead resistance is about 2.6 °C, so conductor size is a measurement decision
- Foil plus braid screen, because the sensor voltage is only tens of millivolts at typical excitation
- Short twist lay length keeps all leads at the same temperature, so their resistances track together
- 0.5–2.5 mm² range: 1.5 mm² gives 1.33 Ω per 100 m lead and about 6.9 °C of two-wire error at that distance
- Class 5 conductors for termination in a transmitter head or a panel terminal
- 3-core and 4-core constructions, plus multi-triple versions for multi-point monitoring
Typical applications
- Pt100 sensors on process plant connected to a temperature transmitter or PLC input card
- Bearing and winding temperature monitoring on motors, pumps and generators
- HVAC, chilled water and building management temperature loops
- Food, pharmaceutical and clean steam applications with hygienic RTD probes
- Calibration laboratory and test bench wiring using four-wire measurement
Ordering options
- 3-core or 4-core construction, or multiple triples in one sheath
- Foil screen with drain wire, or foil plus braid composite
- LSZH sheath to IEC 60754-1 and IEC 61034-2
- Light blue sheath with documented capacitance and inductance for Ex i circuits
- Polyethylene insulation where lower capacitance is required on long runs
Standards manufactured to
- IEC 60751 (industrial platinum resistance thermometers)
- IEC 60228 Class 5 (conductor)
- IEC 60332-1-2 (flame propagation)
- IEC 60079-14 (intrinsically safe installation practice)
- RoHS and REACH compliant compounds
Manufactured to other standards on request. Send the standard number with your RFQ and we will quote against it rather than against a near-equivalent.
Price and availability for Pt100 RTD 3-Wire & 4-Wire Signal Cable
Include cross-section, core count, voltage grade, route length and installation method — those five determine price more than anything else on the page.
- Engineer-reviewed before pricing
- Reference drawings issued with the quotation
- Free sample up to free sample up to 5 m
Pt100 RTD 3-Wire & 4-Wire Signal Cable — frequently asked questions
Why does a three-wire connection cancel lead resistance?
The instrument measures the sensor through one lead and senses the voltage through two others, then subtracts the drop in a shared lead. The cancellation only holds if all three leads have equal resistance, which is why the cores in this cable are built identically and twisted together.
When is a four-wire connection worth the extra core?
When you are calibrating or measuring to better than a few tenths of a degree. A four-wire circuit drives a constant current through one pair and senses voltage through the other, so no current flows in the sense leads and their resistance is irrelevant regardless of length or balance.
What cross-section should I use for a 100 m Pt100 run?
1.5 mm² gives 1.33 Ω per lead at 100 m, which a three-wire input cancels almost entirely. If you must use a two-wire connection, the same run leaves about 6.9 °C of error, so either move to three-wire or increase the section and calibrate the offset out.
Can thermocouple cable be used for a Pt100?
No. Thermocouple extension conductors are nickel alloys with a resistivity roughly forty times that of copper, so they would add tens of ohms of lead resistance and a large error. RTD circuits need copper conductors throughout.
Related technical resources
Chinese Cable Type Codes Explained: YJV, VV, KVV, DJYPVP...
A Chinese cable type code looks like alphabet soup until you know that it is built in blocks: what the insulation is, what the con…
Read → Selection Guide · 10 minVFD and Servo Cable Selection: Why Screened Cable Matters More Than You Think
The cable between a drive and a motor is not carrying a sine wave. It is carrying a train of fast-edged pulses, and that changes w…
Read →